L8-20: Control Fault & Step Out Detect

No.

(Hex.)

Name

Description

Default

(Range)

L8-20

(04C0)

Expert

Control Fault & Step Out Detect

Sets operation after the drive detects a CF fault when A1-02 = 4 [Control Method Selection = Advanced Open Loop Vector].

1

(0 - 2)

If you enter a Stop command but it cannot stop drive operation, the drive will detect CF.

0
Disabled
 
1
CF/STPo Detection Enabled
 
2
CF ALM/Stop

The drive stops DC injection braking as specified by the value of b2-03 [DC Inject Braking Time at Start].

Note:
  • When A1-02 = 4, control will not be stable if you do not do Rotational Auto-Tuning. This can cause CF faults if you ramp to stop. If the drive detects CF, do Rotational Auto-Tuning and Line-to-Line Resistance Tuning. Also, do Line-to-Line Resistance Tuning.

  • If you set A1-02 = 4 and set these parameters, the drive can detect CF because it cannot stop the operation in some load conditions. Make sure that you do Rotational Auto-Tuning and Line-to-Line Resistance Tuning correctly and then set L8-20 = 0.

    • d5-01 = 1 [Torque Control Selection = Torque Control]

    • L3-11 = 1 [Overvoltage Suppression Select = Enabled]

    • Decreased L7-01 to L7-04 [Torque Limit].