No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L8-20
(04C0)
Expert
|
Control Fault & Step Out Detect
|
       
Sets operation after the drive detects a CF fault when A1-02 = 4 [Control Method Selection = Advanced Open Loop Vector].
|
1
(0 - 2)
|
If you enter a Stop command but it cannot stop drive operation, the drive will detect CF.
- 0
- Disabled
-
- 1
- CF/STPo Detection Enabled
-
- 2
- CF ALM/Stop
-
The drive stops DC injection braking as specified by the value of b2-03 [DC Inject Braking Time at Start].
Note:
-
When A1-02 = 4, control will not be stable if you do not do Rotational Auto-Tuning. This can cause CF faults if you ramp to stop. If the drive detects CF, do Rotational Auto-Tuning and Line-to-Line Resistance Tuning. Also, do Line-to-Line Resistance Tuning.
-
If you set A1-02 = 4 and set these parameters, the drive can detect CF because it cannot stop the operation in some load conditions. Make sure that you do Rotational Auto-Tuning and Line-to-Line Resistance Tuning correctly and then set L8-20 = 0.
-
d5-01 = 1 [Torque Control Selection = Torque Control]
-
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
-
Decreased L7-01 to L7-04 [Torque Limit].