No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L8-31
(04E1)
|
LF2 Detection Time
|
       
Sets the LF2 [Output Current Imbalance] detection time.
|
3
(1 – 100)
|
When the output current is unbalanced for longer than the time set in L8-31, the drive detects LF2.
Note:
-
Set L8-29 = 1 [Output Unbalance Detection Sel = Enabled] to enable L8-31.
-
If the drive incorrectly detects LF2, increase L8-31 in 5-unit increments.
-
The keypad shows L8-31 when E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)] in EZ Vector Control.