YASKAWA AC Drive GA700 High Performance Type Technical Manual
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use H2-60, H2-63, H2-66, and H2-69 [Term M1-M2 Secondary Function to Digital Output4 Secondary Func] to set the function of the output signal for which logical operations are performed.
Use H2-61, H2-64, H2-67, and H2-70 [Terminal M1-M2 Logical Operation to DigitalOutput4 Logical Operation] to set the logical operation.
Logical Operation Selection
Logical Operation Expression
Logical Operation Notation
H2-61, H2-64, H2-67, H2-70
0
A=B=1
1
A=1 or B=1
2
A=0 or B=0
3
A=B=0
4
A=B
5
A != B
6
AND(A, )
7
OR(A, )
8
-
On
If you use the function to output logical calculation results, you cannot set H2-01 to H2-04 = 1xx [Inverse Output of xx]. If you do, the drive will detect oPE33 [Digital Output Selection Error].