H2-20
(1540)
Comparator 1 Monitor Selection
Sets the monitor number (Ux-xx) for comparator 1.
102
(000 - 9999)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H2-20 = 102 to monitor U1-02 [Output Frequency].
When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set H2-20 = 1301 to monitor Ud-01.
Refer to 66: Comparator1 and 67: Comparator2 for more information about the comparator function.