YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
H2-26
(1546)
Comparator 2 Monitor Selection
Sets the monitor number (Ux-xx) for comparator 2.
103
(000 - 9999)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H2-26 = 103 to monitor U1-03 [Output Current].
When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set H2-26 = 1301 to monitor Ud-01.
The monitors you can set change when the control method changes.
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal output level from the PLC through MEMOBUS/Modbus communications or the communication option.
Refer to 66: Comparator1 and 67: Comparator2 for more information about the comparator function.