YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
H2-33
(159B)
Comparator1 Protection Selection
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
4
(0 - 4)
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF.
The keypad shows CP1 and the drive continues operation at the current frequency reference.
The output terminal set for Alarm [H2-01 to H2-04 = 10] activates.