No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
n1-05
(0530)
Expert
|
Hunting Prevent Gain in Reverse
|
       
Sets the performance of the hunting prevention function. This parameter adjusts Reverse run. Usually it is not necessary to change this parameter.
|
0.00
(0.00 - 2.50)
|
Note:
When you set this parameter to 0, the value set in n1-02 [Hunting Prevention Gain Setting] is effective when the motor rotates in reverse.
Adjust this parameter in these conditions:
-
When n1-01 = 1, 2 [Hunting Prevention Selection = Enabled (Normal), Enabled (High Carrier Frequency)]: If oscillation occurs when you operate a motor with a light load, increase the setting value in 0.1-unit increments.
-
When n1-01 = 1, 2, if the motor stalls: Decrease the setting value in 0.1-unit increments.