Jump to main content

n1-15: PWM Voltage Offset Calibration

No.

(Hex.)

Name

Description

Default

(Range)

n1-15

(0BF8)

Expert

PWM Voltage Offset Calibration

Sets the calibration method that the drive uses to decrease torque/current ripple.

Determined by A1-02

(0 - 2)

This calibration function lets the drive suppress the torque ripple of a motor. Usually it is not necessary to change this setting.

0
No Calibration
 
1
One Time Calibrate at Next Start
 
2
Calibrate Every Time at Start