No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
n1-16
(0BFB)
|
Hunting Prevention High Fc Gain
|
       
Sets the gain for the hunting prevention function. This parameter functions best with a high carrier frequency. Usually it is not necessary to change this parameter.
|
Determined by o2-04
(0.00 - 2.50)
|
Set n1-01 = 2 [Hunting Prevention Selection = Enabled (High Carrier Frequency)] to enable this function.
If the motor oscillates, set n1-01 = 2. If that does not have an effect, increase this parameter in 0.2-unit increments.