Jump to main content

n1-17: Hunting Prevent High Fc Filter

No.

(Hex.)

Name

Description

Default

(Range)

n1-17

(0BFC)

Expert

Hunting Prevent High Fc Filter

Sets the responsiveness of the hunting prevention function. Usually it is not necessary to change this parameter.

500 ms

(0 - 1000 ms)

When n1-01 = 2 [Hunting Prevention Selection = Enabled (High Carrier Frequency)], if the motor stalls when the load changes, increase the value set in this parameter in 100 ms increments.