No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
n3-02
(0589)
Expert
|
HSB Current Limit Level
|
       
Sets the maximum current output during high-slip braking as a percentage, where E2-01 [Motor Rated Current (FLA)] is 100%. Also set the current suppression to prevent exceeding drive overload tolerance.
|
Determined by C6-01 and L8-38
(0 - 150%)
|
Note:
The upper limit of the setting range changes when the setting for C6-01 [Normal / Heavy Duty Selection] changes.
When you decrease the setting value for current suppression, it will make the deceleration time longer.
-
When you must detect ov [DC Bus Overvoltage] during high-slip braking, set this parameter to a low value.
-
If the motor current increases during high-slip braking, decrease the setting value to prevent burn damage in the motor.
-
The overload tolerance for the drive is 150% for Heavy Duty Rating (HD) and 110% for Normal Duty Rating (ND).