Jump to main content

n4-72: Speed Feedback Mode

No.

(Hex.)

Name

Description

Default

(Range)

n4-72

(1B8C)

Speed Feedback Mode

Sets the requirement for an encoder option when A1-02 = 4 [Control Method Selection = Advanced Open Loop Vector].

0

(0, 1)

You can connect a PG-B3 or PG-X3 encoder option in AOLV control. You can use the encoder option for better speed control precision.

Note:
  • When you use an encoder option in AOLV control to operate machinery, specialized tuning of the drive can be necessary. You should usually set A1-02 = 3 [Control Method Selection = Closed Loop Vector] when you use an encoder option.

  • When you set this parameter to 1, also set the number of PG pulses in F1-01 [Encoder 1 Pulse Count (PPR)].

0
Without Encoder
 
1
With Encoder