YASKAWA AC Drive GA700 High Performance Type Technical Manual
Setting Value
Function
Description
3
User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-72 = 1.