YASKAWA AC Drive GA700 High Performance Type Technical Manual
Setting Value
Function
Description
5
Frequency Detection 2
The terminal activates when the output frequency > L4-01 [Speed Agree Detection Level]. After the terminal activates, the terminal stays activated until the output frequency is at the value of “L4-01 - L4-02”.
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-72 = 1.