Jump to main content

13: Speed Agree 2

Setting Value

Function

Description

13

Speed Agree 2

The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width (+/-)].

Note:
  • The detection function operates in the two motor rotation directions.

  • The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].

ON
The output frequency is in the range of “frequency reference ± L4-04”.
 
OFF
The output frequency is not in the range of “frequency reference ± L4-04”.
 
Figure 1. Speed Agree 2 Time Chart