n7-13: Pull-in Current Switching Time

No.

(Hex.)

Name

Description

Default

(Range)

n7-13

(311D)

Expert

Driving Method Switching Time

Sets a time to enable the pull-in current commands.

100 ms

(0 - 1000 ms)

If the motor oscillates near the speed set in n7-10 [Pull-in Current Switching Speed], decrease the setting value by 20 ms.