Jump to main content

n8-03: Pole Position Detection Time

No.

(Hex.)

Name

Description

Default

(Range)

n8-03

(0542)

Pole Position Detection Time

Sets the length of the Current Starting Time, which is used for Z Pulse Offset Tuning. Usually it is not necessary to change this setting.

1.5 s

(1.5 - 5.0 s)

Sets the length of time of pull-in current when the drive detects the motor magnetic pole of the rotors.

Note:

If the motor oscillates at the time of the polar attraction, increase the value in 0.5 s increments. If the value is too high, the drive can detect oL2 [Drive Overload].