18: Torque Detection 2 (N.O.)

Setting Value

Function

Description

18

Torque Detection 2 (N.O.)

The terminal activates when the drive detects overtorque or undertorque.

Use the L6 [Torque Detection] parameters to set torque detection.

ON
The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer than the time set in L6-06 [Torque Detection Time 2].
 
Note:
  • When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.

  • Refer to L6: Torque Detection for more information.