The speed limit activates and the terminal activates in these conditions:
-
The frequency reference ≥ d2-01 [Frequency Reference Upper Limit]
-
The frequency reference ≤ d2-02 [Frequency Reference Lower Limit] or d2-03 [Analog Frequency Ref Lower Limit].
-
The frequency reference ≤ E1-09 [Minimum Output Frequency] when b1-05 = 1, 2, or 3 [Operation Below Minimum Freq = Baseblock (Motor Coasts), Operate at Minimum Frequency, or Operate at Zero Speed].
-
The frequency reference ≤ Output Freq Lower Limit Level [H3-xx = 9] through analog input.