F6-10: CC-Link Node Address

No.

(Hex.)

Name

Description

Default

(Range)

F6-10

(03B6)

CC-Link Node Address

Sets the node address for CC-Link communication. Restart the drive after you change the parameter setting.

0

(0 - 64)

Note:

Be sure to set a node address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings will cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.

When the only drive is connected, you can connect a maximum of 42 nodes. Follow these rules to connect devices that are not drives:

  • {(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≤ 64

    (a: number of units that occupies 1 node, b: number of units that occupies 2 nodes, c: number of units that occupies 3 nodes, d: number of units that occupies 4 nodes)

  • {(16 × A) + (54 × B) + (88 × C)} ≤ 2304

    (A: number of remote I/O nodes (64 max.), B: number of remote device nodes (42 max.), C: number of local nodes (26 max.))