F6-20
(036B)
MECHATROLINK Station Address
Sets the station address for MECHATROLINK communication. Change the parameter then cycle power on the drive.
0021h
(MECHATROLINK-II: 0020h - 003Fh, MECHATROLINK-III: 0003h - 00EFh)
The setting range changes if using MECHATROLINK-II or MECHATROLINK-III:
MECHATROLINK-II (SI-T3) range: 20 to 3F
MECHATROLINK-III (SI-ET3) range: 03 to EF
Be sure to set a node address that is different than all other node addresses. Incorrect parameter settings will cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.
The drive detects AEr errors when the station address is 20 or 3F.