MEMOBUS/Modbus Multi-Function AI1 to 3 Function Selection

Let the MFAI function be assigned to MEMOBUS/Modbus register 15C1 to 15C3 (Hex.) [Mbus Reg 15C1h through 15C3h Input Function]. Use H3-40 to H3-42 [Mbus Reg 15C1h through 15C3h Input Function] to set the function and use H3-43 [Mbus Reg Inputs FilterTime Const] to set the input filter.

Table 1. MEMOBUS Multi-Function AI Command Register

Register No.

(Hex.)

Name

Range 1

Parameter

15C1

Mbus Reg 15C1h Input Function

-32767 to 32767

H3-40

15C2

Mbus Reg 15C2h Input Function

-32767 to 32767

H3-41

15C3

Mbus Reg 15C3h Input Function

-32767 to 32767

H3-42

 
Figure 1. Functional Block Diagram for MEMOBUS Multi-Function AI Command 1
Note:
  • Refer to H3-xx “MFAI Setting Values” for the analog input setting values.

  • When you will not use the terminal, set H3-40 to H3-42 = F. The through mode function is not supported.

  • You cannot use H3-40 to H3-42 to set these MFAI terminals:

     

    H3-xx Setting Value

    Function

    0

    Frequency Reference

    1

    Frequency Gain

    2

    Auxiliary Frequency Reference 1

    3

    Auxiliary Frequency Reference 2

    30

    DWEZ Analog Input 1

    31

    DWEZ Analog Input 2

    32

    DWEZ Analog Input 3

1