No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
H3-08
(0416)
RUN
|
Terminal A3 Bias Setting
|
       
Sets the bias of the analog signal input to MFAI terminal A3.
|
0.0%
(-999.9 - +999.9%)
|
When 0 V (4 mA or 0 mA) is input, this parameter sets the bias for the function set for terminal A3 as a percentage.
Use this parameter and H3-07 [Terminal A3 Gain Setting] to adjust the characteristics of the analog input signal to terminal A3.