Calibrate Meters Connected to MFAO Terminals FM and AM

To calibrate the meters connected to terminals FM and AM, use these parameters:

  • H4-02 [Terminal FM Analog Output Gain]

  • H4-03 [Terminal FM Analog Output Bias]

  • H4-05 [Terminal AM Analog Output Gain]

  • H4-06 [Terminal AM Analog Output Bias]

Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08 [Terminal AM Signal Level Select] to select the voltage output and current output.

 

No.

Name

Range

Default

H4-02

Terminal FM Analog Output Gain

-999.9 - +999.9%

100.0%

H4-03

Terminal FM Analog Output Bias

-999.9 - +999.9%

0.0%

H4-05

Terminal AM Analog Output Gain

-999.9 - +999.9%

50.0%

H4-06

Terminal AM Analog Output Bias

-999.9 - +999.9%

0.0%

H4-07

Terminal FM Signal Level Select

0: 0 to 10 Vdc

1: -10 to +10 Vdc

2: 4 to 20 mA

0

H4-08

Terminal AM Signal Level Select

0: 0 to 10 Vdc

1: -10 to +10 Vdc

2: 4 to 20 mA

0

Figure 1 and Figure 2 show the gain and bias.

Figure 1. Analog Output Gain/Bias Configuration Example 1

For example, when the parameter value set to analog output is 0, and a 3 V signal is output to terminal FM, H4-03 [Terminal FM Analog Output Bias] is set to 30%.

Figure 2. Analog Output Gain/Bias Configuration Example 2

Calibrate Terminal FM

Stop the drive to calibrate meters. Use this procedure to calibrate:

  1. Show H4-02 [Terminal FM Analog Output Gain] on the keypad.

    Terminal FM outputs the analog signal when the monitor item that you set in H4-01 [Terminal FM Analog Output Select] is 100%.

  2. Adjust H4-02 while referencing the meter scale connected to terminal FM.

  3. Show H4-03 [Terminal FM Analog Output Bias] on the keypad.

    Terminal FM outputs the analog signal when the monitor item that you set in H4-01 is 0%.

  4. Adjust H4-03 while referencing the meter scale connected to terminal FM.

Calibrate Terminal AM

Stop the drive to calibrate meters. Use this procedure to calibrate:

  1. Show H4-05 [Terminal AM Analog Output Gain] on the keypad.

    Terminal AM outputs the analog signal when the monitor item that you set in H4-04 [Terminal AM Analog Output Select] is 100%.

  2. Adjust H4-05 while referencing the meter scale connected to terminal AM.

  3. Show H4-06 [Terminal AM Analog Output Bias] on the keypad.

    Terminal AM outputs the analog signal when the monitor item that you set in H4-04 is 0%.

  4. Adjust H4-06 while referencing the meter scale connected to terminal AM.