H4-01
(041D)
Terminal FM Analog Output Select
Sets the monitoring number (Ux-xx) to be output from MFAO terminal FM.
102
(000 - 9999)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02 [Output Frequency].
When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set H4-01 = 1301 to monitor Ud-01.
You cannot use all of the monitors in all of the control methods.
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal FM output level from the PLC through MEMOBUS/Modbus communications or the communication option.