No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
H4-05
(0421)
RUN
|
Terminal AM Analog Output Gain
|
       
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
|
50.0%
(-999.9 - +999.9%)
|
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-08 [Terminal AM Signal Level Select].
Example settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a maximum voltage of 10 V will be 200% of the drive rated current.