H4-20: Analog Power Monitor 100% Level

No.

(Hex.)

Name

Description

Default

(Range)

H4-20

(0B53)

Analog Power Monitor 100% Level

Sets the level at 10 V when U1-08 [Output Power] is set for analog output.

0.00 kW

(0.00 - 1000.0 kW)

Note:
  • When H4-20 = 0.00 kW, the output power monitor 10 V level = motor rated power. The setting changes when the A1-02 [Control Method Selection] value changes:

    • A1-02 = 0, 1 [V/f, CL-V/f]: E2-11 [Motor Rated Power]

    • A1-02 = 2, 3, 4 [OLV, CLV, AOLV]: E2-11 [Motor Rated Power]

    • A1-02 = 5, 6, 7 [OLV/PM, AOLV/PM, CLV/PM]: E5-02 [PM Motor Rated Power]

    • A1-02 = 8 [EZOLV]: E9-07 [Motor Rated Power]

  • On drive models 2xxx, and 4002 to 4675, the setting unit is 0.01 kW. The setting range is 0.00 kW to 650.00 kW.