No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
o2-04
(0508)
|
Drive Model (KVA) Selection
|
       
Sets the Drive Model code. Set this parameter after replacing the control board.
|
Determined by the drive
(-)
|
| Notice |
|
Set o2-04 [Drive Model (KVA) Selection] correctly.
If you set this parameter incorrectly, it will decrease drive performance, cause the protection function to operate incorrectly, and cause damage to the drive.
|
These tables list the relation between o2-04 setting values and drive models.
Table 1. Three-Phase 200 V Class
|
Drive Model
|
o2-04 Setting
|
|
2004
|
62
|
|
2006
|
63
|
|
2008
|
64
|
|
2010
|
65
|
|
2012
|
66
|
|
2018
|
67
|
|
2021
|
68
|
|
2030
|
6A
|
|
2042
|
6B
|
|
2056
|
6D
|
|
2070
|
6E
|
|
2082
|
6F
|
|
2110
|
70
|
|
2138
|
72
|
|
2169
|
73
|
|
2211
|
74
|
|
2257
|
75
|
|
2313
|
76
|
|
2360
|
77
|
|
2415
|
78
|
Table 2. Three-Phase 400 V Class
|
Drive Model
|
o2-04 Setting
|
|
4002
|
92
|
|
4004
|
93
|
|
4005
|
94
|
|
4007
|
95
|
|
4009
|
96
|
|
4012
|
97
|
|
4018
|
99
|
|
4023
|
9A
|
|
4031
|
9C
|
|
4038
|
9D
|
|
4044
|
9E
|
|
4060
|
9F
|
|
4075
|
A1
|
|
4089
|
A2
|
|
4103
|
A3
|
|
4140
|
A4
|
|
4168
|
A5
|
|
4208
|
A6
|
|
4250
|
A7
|
|
4296
|
A8
|
|
4371
|
A9
|
|
4389
|
AA
|
|
4453
|
AC
|
|
4568
|
AD
|
|
4675
|
AE
|
|
4810
|
B0
|
|
4930
|
B1
|
|
4H11
|
B2
|
|
4H12
|
B3
|