YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-23
(11F8)
RUN
External 24V Powerloss Detection
Sets the function to give a warning if the backup external 24 V power supply turns off when the main circuit power supply is in operation.
0
(0, 1)
The drive will not run when it is operating from one 24-V external power supply.
The drive does not detect the loss of the 24-V external power supply.
The keypad shows the L24v [Loss of External Power 24 Supply] indicator if the drive detects the loss of the 24-V external power supply.
A minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Alarm].