YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
o2-26
(1563)
Alarm Display at Ext. 24V Power
When you connect a backup external 24 V power supply, this parameter sets the function to trigger an alarm when the main circuit power supply voltage decreases.
0
(0, 1)
The drive will not detect EP24v [External Power 24V Supply] if the main circuit power supply voltage decreases. The [Ready] light on the LED Status Ring flashes quickly to identify that drive operation is not possible.
The drive detects EP24v when the main circuit power supply voltage decreases.
A minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Alarm].