YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
o5-15
(1E82)
RUN
Trigger Type Selection
Sets the type of trigger for the short-term data log. This parameter is only available when you use an LCD keypad.
0
(0, 1)
A digital signal inside the drive will act as the trigger.
An analog signal inside the drive will act as the trigger.
There are no detection width and detection time settings for the analog trigger in the data log function. If variations in the analog signal are a problem, set o5-15 = 0 and o5-16 = 66, 67 [Digital Trigger Object = Comparator 1, 2]. Use H2-20 [Comparator 1 Monitor Selection] to H2-32 [Comparator 1 Filter Time] to set the conditions for the comparator function.