No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
T1-05
(0705)
|
Motor Base Frequency
|
       
Sets the base frequency (Hz) of the motor.
|
60.0 Hz
(0.0 - 590.0 Hz)
|
When Auto-Tuning is carried out, the value of T1-05 is set to E1-04 [Maximum Output Frequency]. If T1-05 < 40 Hz, E1-04 = 40 Hz. If you operate the drive at a speed that is higher than the base frequency, or if you operate in the field weakening range, set E1-04 (E3-04 for motor 2) to the maximum output frequency after you complete Auto-Tuning.