Jump to main content

T1-09: Motor No-Load Current

No.

(Hex.)

Name

Description

Default

(Range)

T1-09

(0709)

Motor No-Load Current

Sets the no-load current of the motor.

-

(0 A - T1-04; max. of 2999.9)

Note:

The display units are different for different models:

  • Models 2004 - 2042, 4002 - 4023: 0.01 A

  • Models 2056 - 2415, 4031 - 4H12: 0.1 A

The value shown is the no-load current that the drive automatically calculates from the values set in T1-02 [Motor Rated Power] and T1-04 [Motor Rated Current]. Set the no-load current shown on the motor test report. If the motor test report is not available, do not change this parameter.