H6-08
(043F)
Terminal RP Minimum Frequency
Sets the minimum frequency of the pulse train signal that terminal RP can detect.
0.5 Hz
(0.1 - 1000.0 Hz)
When you input a pulse train frequency that is less than the value of H6-08, the pulse train input is 0.0 Hz.
Set H6-01 = 0, 1, or 2 [Terminal RP Pulse Train Function = Frequency Reference, PID Feedback Value, or PID Setpoint Value] to enable this parameter.
When H6-01 = 3 [Speed Feedback (V/F Control)], the drive applies the setting of F1-14 [Encoder Open-Circuit Detect Time] to the minimum frequency.