Refer to Table 1 and Table 2 for a list of Output terminals and functions.

Table 1. Control Circuit Output Terminals

Type

Terminal

Name (Default)

Function (Signal Level)

Digital Outputs

MA

N.O. output

(Fault)

  • Relay output

  • 30 Vdc, 10 mA to 1 A

  • 250 Vac, 10 mA to 1 A

  • Minimum load: 5 V, 10 mA (Reference value)

MB

N.C. output

(Fault)

MC

Digital output common

Multi-function Photocoupler Outputs

P1

Multi-function photocoupler output 1

(During RUN)

  • Photocoupler output

  • 48 V, 2 mA to 50 mA

Note:

Connect a flywheel diode as shown in Figure 1 when you drive a reactive load, for example a relay coil. Make sure that the diode rating is larger than the circuit voltage.

C1

P2

Multi-function photocoupler output 2

(Speed agree 1)

C2

Figure 1. Connecting a Flywheel Diode
  • External power, 48 V maximum
  • Flywheel diode
  • Coil
  • 50 mA or less
Table 2. Control Circuit Monitor Output Terminals

Type

Terminal

Name (Default)

Function (Signal Level)

Monitor Output

MP

Pulse train output

(Output frequency)

32 kHz (maximum)1

AM

Analog monitor output

(Output frequency)

Select voltage or current output.

  • 0 V to 10 V/0% to 100%

  • 4 mA to 20 mA (Receiver recommended impedance: 250 Ω)

Note:

Use jumper S5 and H4-07 [Terminal AM Signal Level Select] to set the signal type.

AC

Monitor common

0 V

 
1

Refer to Pulse Train Output for more information.