Table 1. Factory-Recommended Branch Circuit Protection: Three-Phase 200 V Class Drive Model Maximum Applicable Motor Output kW (HP) Time Delay Fuse Semiconductor Protection Fuse Rated Current Manufacturer: EATON/Bussmann ND HD Class J, CC, and T Fuse Rated Current A Model Fuse Rated Current A 2001 0.2 (1/6) 0.1 (1/6) 3 FWH-25A14F 25 2002 0.4 (1/4) 0.2 (1/4) 3.5 FWH-25A14F 25 2004 0.75 (3/4) 0.4 (1/2) 6 FWH-25A14F 25 2006 1.1 (1.5) 0.75 (1) 10 FWH-25A14F 25 2008 1.5 (2) 1.1 (1.5) 12 FWH-70B 70 2010 2.2 (3) 1.5 (2) 15 FWH-70B 70 2012 3.0 (4) 2.2 (3) 20 FWH-70B 70 2018 3.7 (5) 3.0 (4) 30 FWH-90B 90 2021 5.5 (7.5) 3.7 (5) 35 FWH-90B 90 2030 7.5 (10) 5.5 (7.5) 50 FWH-100B 100 2042 11 (15) 7.5 (10) 70 FWH-150B 150 2056 15 (20) 11 (15) 90 FWH-200B 200 2070 18.5 (25) 15 (20) 110 FWH-200B 200 2082 22 (30) 18.5 (25) 125 FWH-225A 225