This section gives information about the Auto-Tuning mode for EZ Open Loop Vector Control. Auto-Tuning will set the E9-xx parameters. Table 1. EZ Tuning Mode Selection Mode Parameter Settings Application Conditions and Benefits Applicable Control Method (A1-02 Setting) Motor Parameter Setting T4-01 = 0 Applicable when driving an induction motor or a PM motor Suitable for derating torque applications, for example fans and pumps. EZOLV (8) Line-to-Line Resistance T4-01 = 1 After Auto-Tuning, the wiring distance between the drive and motor changed by 50 m or more. When the motor output and drive capacity are different. EZOLV (8) Auto-Tuning Input Data in EZ Open Loop Vector Control Method To do Auto-Tuning, input data for the items in >Table 2 that have an "x". Before you start Auto-Tuning, prepare the motor test report or record the information from the motor nameplate as a reference. Table 2. Auto-Tuning Input Data in EZ Open Loop Vector Control Method Input Data Parameter Unit Auto-Tuning Mode (T4-01 Setting) Motor Parameter Setting (0) Line-to-Line Resistance (1) Motor Type Selection T4-02 - x - Motor Max Revolutions T4-03 min-1 x - Motor Rated Revolutions T4-04 min-1 x - Motor Rated Frequency T4-05 Hz x - Motor Rated Voltage T4-06 V x - Motor Rated Current (FLA) T4-07 A x x PM Motor Rated Power (kW) T4-08 kW x x Number of Motor Poles T4-09 - x -