Note:

During a test run, make sure that U1-03 [Output Current] is not too high.

Connect the motor and machine, then do the test run with the same procedure that you used for the no-load test run.

  1. Energize the drive, or push [ESC key] to show the frequency reference screen.
  2. Use [Up arrow key] / [Down arrow key] / [Left Arrow Key] / [Right Arrow Key (RESET Key)] to set d1-01 = 6.00 [Frequency Reference 1 = 6.00 Hz], then push [Enter key] .
  3. Push [LO/RE selection key] to illuminate the LOCAL/REMOTE LED.
  4. Push [RUN key].

    The RUN indicator illuminates, and the motor runs at 6.00 Hz in the forward direction.

  5. Make sure that the motor is rotating in the correct direction and that the drive does not show a fault.

    If the drive detects a fault, remove the cause.

  6. Push [Up arrow key] to increase the frequency reference value.

    Change the setting value in increments of 10 Hz if necessary and examine the response.

    Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz

  7. Each time you increase the setting value, use U1-03 [Output Current] to check the drive output current.

    When the output current of the drive is not more than the motor rated current, the status is correct.

  8. Make sure that the motor rotates correctly, then push [STOP key].

    The RUN LED flashes and goes off when the motor stops completely.

  9. Change the frequency reference and direction of motor rotation, and make sure that there are no unusual sounds or vibrations.
  10. If the control function causes hunting or oscillation errors, adjust the settings to stop the errors.