Jump to main content

Standard Connection Diagram

Wire the drive as specified by Figure 1.

Note:

Do not connect the AC control circuit ground to the drive enclosure. Failure to obey can cause incorrect control circuit operation.

Figure 1. Standard Drive Connection Diagram
12345678910111213141516171819
1

Set the wiring sequence to de-energize the drive with the MFDO. If the drive outputs a fault during fault restart when you use the fault restart function, set L5-02 = 1 [Fault Contact at Restart Select = Always Active] to de-energize the drive. Be careful when you use a cut-off sequence. The default setting for L5-02 is 0 [Active Only when Not Restarting].

2

When you install a DC reactor, you must remove the jumper between terminals +1 and +2.

3

When you use a regenerative converter or regenerative unit, set L8-55 = 0 [Internal DB TransistorProtection = Disable]. If L8-55 = 1 [Protection Enabled], the drive will detect rF [Braking Resistor Fault].

4

When you use a regenerative converter, regenerative unit, braking resistor, or braking resistor unit, set L3-04 = 0 [Stall Prevention during Decel = Disabled]. If L3-04 = 1 [General Purpose], the drive could possibly not stop in the specified deceleration time.

5

When you use an ERF-type braking resistor, set L8-01 = 1 [3% ERF DB Resistor Protection = Enabled] and set a wiring sequence to de-energize the drive with the MFDO.

6

Cooling fan wiring is not necessary for self-cooling motors.

7

Connect peripheral options to terminals -, +1, +2, B1, and B2.

8

Connect a 24 V power supply to terminals PS-AC to operate the control circuit while the main circuit power supply is OFF.

9

To set the MFDI power supply (Sinking/Sourcing Mode or internal/external power supply), install or remove a jumper between terminals SC-SP or SC-SN depending on the application.

  • Sinking Mode, Internal power supply: Install the jumper to close the circuit between terminals SC-SP.

  • Sourcing Mode, Internal power supply: Install the jumper to close the circuit between terminals SC-SN.

  • External power supply: Remove the jumper from the MFDI terminals. It is not necessary to close the circuit between terminals SC-SP and terminals SC-SN.

10
11

The maximum output current capacity for terminal +V on the control circuit is 20 mA.

12

DIP switch S1 sets terminal A2 for voltage or current input. The default setting for S1 is current input (“I” side).

13

Do not ground the control circuit terminals AC or connect them to the drive chassis.

14

Connect the positive lead from an external 24 Vdc power supply to terminal PS and the negative lead to terminal AC.

15

Set DIP switch S2 to “ON” to enable the termination resistor in the last drive in a MEMOBUS/Modbus network.

16

Use only Sourcing Mode for Safe Disable input.

17

Use multi-function analog monitor outputs with analog frequency meters, ammeters, voltmeters, and wattmeters. Do not use monitor outputs with feedback-type signal devices.

18

Jumper S5 sets terminal AM for voltage or current output. The default setting for S5 is voltage output (“V” side).

19

Disconnect the wire jumpers between H1 and HC and H2 and HC to use the Safe Disable input.