Jump to main content

Single-Phase 200 V Class

 

Model

Terminal

Recomm. Gauge

mm2

Applicable Gauge

mm2

Wire Stripping Length 1

mm

Terminal Screw

Size and Shape

Tightening Torque

N∙m (lbf∙in)

B001

L/L1, N/L2

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

U/T1, V/T2, W/T3

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

-, +1

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

B1, B2

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

2 2

2 2

-

M3.5

0.8 - 1.0

(7.1 - 8.9)

B002

L/L1, N/L2

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

U/T1, V/T2, W/T3

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

-, +1

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

B1, B2

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

2 2

2 2

-

M3.5

0.8 - 1.0

(7.1 - 8.9)

B004

L/L1, N/L2

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

U/T1, V/T2, W/T3

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

-, +1

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

B1, B2

2

2

6.5

M3

0.5 - 0.6

(4.4 - 5.3)

2 2

2 2

-

M3.5

0.8 - 1.0

(7.1 - 8.9)

B006

L/L1, N/L2

2

2 - 3.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

U/T1, V/T2, W/T3

2

2 - 3.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

-, +1

2

2 - 3.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

B1, B2

2

2 - 3.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

3.5 2

2 - 5.5 2

-

M4

1.2 - 1.5

(10.6 - 13.3)

B010

L/L1, N/L2

3.5

2 - 5.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

U/T1, V/T2, W/T3

2

2 - 3.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

-, +1

3.5

2 - 5.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

B1, B2

2

2 - 3.5

8

M3

0.5 - 0.6

(4.4 - 5.3)

3.5 2

2 - 5.5 2

-

M4

1.2 - 1.5

(10.6 - 13.3)

B012

L/L1, N/L2

5.5

3.5 - 8

10

M4

1.5 - 1.7

(13.5 - 15)

U/T1, V/T2, W/T3

2

2 - 3.5

10

M4

1.5 - 1.7

(13.5 - 15)

-, +1

5.5

3.5 - 8

10

M4

1.5 - 1.7

(13.5 - 15)

B1, B2

2

2 - 3.5

10

M4

1.5 - 1.7

(13.5 - 15)

3.5 2

2 - 5.5 2

-

M4

1.2 - 1.5

(10.6 - 13.3)

B018

L/L1, N/L2

8

3.5 - 14

10

M4

1.5 - 1.7

(13.5 - 15)

U/T1, V/T2, W/T3

3.5

2 - 5.5

10

M4

1.5 - 1.7

(13.5 - 15)

-, +1

8

3.5 - 14

10

M4

1.5 - 1.7

(13.5 - 15)

B1, B2

2

2 - 3.5

10

M4

1.5 - 1.7

(13.5 - 15)

5.5 2

4 - 8 2

-

M5

2.0 - 2.5

(17.7 - 22.1)

 
1

Remove insulation from the ends of wires to expose the length of wire shown.

2

If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm2 (copper wire).

  • 8-4NS from JST Mfg. Co., Ltd.

  • R8-4S from NICHIFU Co.,Ltd.

  • P10-8R from PANDUIT Corp.