Hunting or oscillation at mid-range speeds (10 Hz to 40 Hz)
|
n1-02 [Hunting Prevention Gain Setting]
|
-
If torque is not sufficient with heavy loads, decrease the setting value.
-
If hunting or oscillation occur with light loads, increase the setting value.
-
If hunting occurs with a low-inductance motor, for example a motor with a larger frame size or a high-frequency motor, lower the setting value. Set n1-01 = 1 [Hunting Prevention Selection = Enabled].
|
1.00
|
0.10 - 2.00
|
-
The volume of the motor excitation sound is too high.
-
Hunting or oscillation at low speeds (10 Hz or lower), or at mid-range speeds (10 Hz to 40 Hz)
|
C6-02 [Carrier Frequency Selection]
|
-
If the volume of the motor excitation sound is too high, increase the carrier frequency.
-
If hunting or oscillation occur at low or mid-range speeds, decrease the carrier frequency.
|
1 (2 kHz) 1
|
1 to upper limit value
|
|
|
C4-02 [Torque Compensation Delay Time]
|
-
If torque or speed response are slow, decrease the setting value.
-
If hunting or oscillation occur, increase the setting value.
|
200 ms 2
|
100 ms to 1000 ms
|
|
|
C4-01 [Torque Compensation Gain]
|
-
If torque at low speeds (10 Hz or lower) is not sufficient, increase the setting value.
-
If hunting or oscillation occur with light loads, decrease the setting value.
|
1.00
|
0.50 - 1.50
|
|
|
C4-01 [Torque Compensation Gain]
|
Decrease the setting value in these conditions:
-
Drive trips at overload.
-
Hunting or oscillation.
|
1.00
|
0.00 - 1.00
|
|
|
|
-
If torque at low speeds (10 Hz or lower) is not sufficient, increase the setting value.
-
If there is large initial vibration at start up, decrease the setting value
|
-
E1-08: 16.0 V 3
-
E1-10: 12.0 V 3
|
Default setting +/- 5 V 4
|
|
Speed precision is unsatisfactory.
|
C3-01 [Slip Compensation Gain]
|
Set E2-01 [Motor Rated Current], E2-02 [Motor Rated Slip], and E2-03 [Motor No-Load Current], then adjust C3-01.
|
0.0 (no slip compensation)
|
0.5 - 1.5
|