Unsatisfactory motor performance
|
E1-xx parameters, E5-xx parameters
|
-
Check the settings for E1-06, E1-04 [Base Frequency, Maximum Output Frequency].
-
Check the E5-xx and make sure that you set all motor data correctly.
Note:
Do not set E5-05 [PM Motor Resistance (ohms/phase)] to a line-to-line resistance value.
-
Do Auto-Tuning.
|
-
|
-
|
|
Unsatisfactory motor torque and speed response
|
n8-55 [Motor to Load Inertia Ratio]
|
Adjust to align the load inertia ratio of the motor and machine.
|
0
|
Near the load inertia ratio.
|
|
n8-45 [Speed Feedback Detection Gain]
|
Decrease the setting value in increments of 0.05.
|
0.80
|
-
|
|
C4-01 [Torque Compensation Gain]
|
Adjust the setting value.
Note:
If you set this value too high, it can cause overcompensation and motor oscillation.
|
0.00
|
1.00
|
|
|
n8-51 [Pull-in Current @ Accel/Decel]
|
Increase the setting value in increments of 5%.
|
50%
|
-
|
|
|
Use DC Injection Braking at start.
Note:
This can cause the motor to rotate in reverse for approximately 1/8 of a turn at start.
|
|
|
|
n8-55 [Motor to Load Inertia Ratio]
|
Increase the setting value.
Note:
When you operate a single motor or with a minimum quantity of inertia, if you set this value too high, it can cause motor oscillation.
|
0
|
Near the load inertia ratio.
|
|
There is too much current during deceleration.
|
n8-79 [Pull-in Current at Deceleration]
|
Set n8-79 < n8-51.
|
50%
Note:
When n8-79 = 0, the drive will apply the n8-51 setting to the pull-in current during deceleration.
|
Decrease in increments of 5%.
|
|
Stalling or oscillation occurs when you apply the load during constant speed
|
n8-47 [Pull-in Current Comp Filter Time]
|
Decrease the setting value in increments of 0.2 s.
|
5.0 s
|
-
|
|
n8-48 [Pull-in/Light Load Id Current]
|
Increase the setting value in increments of 5%.
|
30%
|
-
|
|
n8-55 [Motor to Load Inertia Ratio]
|
Increase the setting value.
Note:
When you operate a single motor or with a minimum quantity of inertia, if you set this value too high, it can cause motor oscillation.
|
0
|
Near the load inertia ratio.
|
|
Hunting or oscillation
|
n8-45 [Speed Feedback Detection Gain]
|
Increase the setting value in increments of 0.05.
|
0.80
|
-
|
|
The drive detects STPo [Motor Step-Out Detected] fault when the load is not too high.
|
|
-
Adjust the setting value.
-
Examine the motor code on the motor nameplate or the data sheet, then set correct values for E5-09 or E5-24.
|
1
|
-
Yaskawa motor
Set the motor code from the motor nameplate.
-
Motor from another manufacturer
Set the values from the test report.
|
|
The drive detected stalling or STPo [Motor Step-Out Detected] at high speed and maximum output voltage.
|
n8-62 [Output Voltage Limit Level]
|
Set to a value lower than the actual input voltage.
|
|
-
|