USB Terminal Pass-through
|
Pass-through point to connect a USB cable to the drive to support the DriveWizard PC tool and the DriveWizard Mobile App. Uses a USB cable (USB standard 2.0, type A - mini-B) to connect the drive to a PC, Android smartphone, or tablet.
|
|
B
|
RUN Key
![[RUN key]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331198.svg)
|
Starts the drive in LOCAL Mode.
Starts the operation in Auto-Tuning Mode.
Note:
Before you use the keypad to operate the motor, push on the keypad to set the drive to LOCAL Mode.
|
|
C
|
STOP Key
![[STOP key]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331167.svg)
|
Stops drive operation.
Note:
Uses a stop-priority circuit. Push to stop the motor. This will also apply when a Run command (REMOTE Mode) is active at an external Run command source. To disable priority, set o2-02 = 0 [STOP Key Function Selection = Disabled].
|
|
D
|
LO/RE LED
![[LO/RE LED]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331197.svg)
|
Illuminated: The keypad controls the Run command (LOCAL Mode).
OFF: The control circuit terminal or serial transmission device controls the Run command (REMOTE Mode).
Note:
-
LOCAL: Use the keypad to operate the drive. Use the keypad to enter Run/Stop commands and the frequency reference command.
-
REMOTE: Use the control circuit terminal or serial transmission to operate the drive. Use the frequency reference source entered in b1-01 and the Run command source selected in b1-02.
|
|
E
|
ALM/ERR LED
![[ALM/ERR LED]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331196.svg)
|
Illuminated: The drive detects a fault.
OFF: There are no drive faults or alarms.
Flashing:
-
Alarm
-
Operation Errors
-
An Auto-Tuning error
Note:
The LED will illuminate to identify a fault if the drive detects a fault and an alarm at the same time.
|
|
F
|
READY LED
![[READY LED]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331195.svg)
|
Illuminated: The drive is operating or is ready for operation.
OFF:
-
The drive detects a fault.
-
There is no fault and the drive received a Run command, but the drive cannot run. For example, in Programming Mode.
Flashing: The drive is in STo [Safe Torque OFF] condition.
Flashing quickly: The voltage of the main circuit power supply is not in the drive nameplate specifications, and the external 24 V power supply is providing the only power to the drive.
|
|
G
|
RUN LED
![[RUN LED]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331194.svg)
|
Illuminated: The drive is in normal operation.
OFF: The drive is stopped.
Flashing:
-
The drive is decelerating to stop.
-
The drive received a Run command with a frequency reference of 0 Hz, but the drive is not set for zero speed control
Flashing quickly:
-
The drive received a Run command from the MFDI terminals while in LOCAL Mode and it switched to REMOTE Mode.
-
The drive received a Run command from the MFDI terminals when the drive is not in Drive Mode.
-
The drive received a Fast Stop command.
-
The safety function shut off the drive output.
-
You pushed on the keypad while the drive is operating in REMOTE Mode.
-
The drive is energized with an active Run command and b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command].
|
|
H
|
Left Arrow Key
![[Left Arrow Key]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331193.svg)
|
Moves the cursor to the left.
|
|
Up Arrow Key/Down Arrow Key
/ ![[Down arrow key]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331191.svg)
|
|
|
Right Arrow Key (RESET)
![[Right Arrow Key (RESET Key)]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331190.svg)
|
|
|
ENTER Key
![[ENTER Key]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331693.svg)
|
-
Enters parameter values and settings.
-
Selects each mode, parameter, and set value.
|
|
I
|
ESC Key
![[ESC key]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331189.svg)
|
|
|
J
|
LED Display
|
Shows parameters, errors, and other data.
|
|
K
|
LO/RE Selection Key
![[LO/RE Selection Key]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331166.svg)
|
Switches drive control for the Run command and frequency reference between the keypad (LOCAL) and an external source (REMOTE).
Note:
-
The LOCAL/REMOTE Selection Key continuously stays enabled after the drive stops in Drive Mode. If the application must not switch from REMOTE to LOCAL because it will have a negative effect on system performance, set o2-01 = 0 [LO/RE Key Function Selection = Disabled] to disable .
-
The drive will not switch between LOCAL and REMOTE when it is receiving a Run command from an external source.
|
|
L
|
REV LED
![[REV LED]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331208.svg)
|
Illuminated: The drive received a Reverse run command.
|
|
M
|
DWEZ LED
![[DWEZ LED]](https://www.yaskawaindia.in/yaskawa_new_admin/uploads/ckuploads/0002331207.svg)
|
Illuminated: The drive is In DriveWorksEZ operation.
|
|
N
|
RJ-45 Connector
|
Connects to the drive. Use an RJ-45 8-pin straight UTP CAT5e extension cable to install the keypad in a different location than the drive.
|