Make sure that the keypad shows READY LED before you start to operate the motor.
|
| |
12
|
To give the Run command and frequency reference from the keypad, push to set to LOCAL Mode (when in LOCAL Mode, the LO/RE LED illuminates).
|
| |
13
|
If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
|
| |
14
|
Set Heavy Duty or Normal Duty Mode with C6-01 [Normal / Heavy Duty Selection] to conform to the load condition.
|
| |
15
|
Set E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload (oL1) Protection] correctly for motor thermal protection.
|
| |
16
|
Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency reference (in REMOTE Mode, the LO/RE LED turns OFF).
|
| |
17
|
When you use terminal A1 for the frequency reference:
-
Set H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0 to 10 V (Lower Limit at 0), 0 V to 10 V (Without Lower Limit)].
-
Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].
|
| |
18
|
When you use terminal A2 for the frequency reference:
-
Voltage input
-
Set DIP Switch S1 on the drive to “V”.
-
Set H3-09 = 0, 1 [Terminal A2 Signal Level Select = 0-10V (LowLim=0), 0-10V (Without Lower Limit)].
-
Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].
-
Current input
-
Set DIP Switch S1 on the drive to “I”.
-
Set H3-09 = 2, 3 [Terminal A2 Signal Level Select = 4 to 20 mA, 0 to 20 mA].
-
Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].
|
| |
19
|
Make sure that the frequency reference gets to the necessary minimum and maximum values.
If drive operation is incorrect, make these adjustments:
-
Gain Adjustment
Set the maximum voltage and current values, then adjust the analog input gain until the frequency reference is at the necessary value.
-
Bias adjustment
Set the maximum voltage and current values, then adjust the analog input gain until the frequency reference is at the necessary value.
|