These operations are available in Drive Mode:
-
Operate and stop the drive
-
Show the drive status monitors (for example, frequency reference, output frequency, output current, and output voltage)
-
Show the alarm content
-
Show the alarm history
Note:
To operate the drive, select Drive Mode. You can switch to other modes when the drive stops, but the drive must be in Drive Mode to start operation.
These steps show how to set the frequency reference source to LOCAL (keypad) and change the frequency reference from 0 Hz to 6 Hz.
Figure 1. Frequency Reference Setting in Drive Mode
Note:
To prevent an incorrect setting, after you enter the frequency reference, you must push the ENTER key to change the frequency reference. Set o2-05 = 1 [Home Mode Freq Ref Entry Mode = Immediate / MOP-style] to change the frequency reference value without pushing the ENTER key.