Drive Mode and Programming Mode

The keypad display of this drive has two modes: Drive Mode and Programming Mode.

  • Drive Mode

    Use this mode to operate the drive. These operations are available:

    • Monitor operation statuses (for example, output frequency, output current, and output voltage)

    • Set the parameters that you can change while the drive is operating (for example, d1-01 to d1-17). Refer to Parameter Details for more information.

  • Programming Mode

    Parameter Setting Mode These operations are available:

    • Examine and set the parameters that are not at default settings (Verify Mode)

    • See and set the basic parameters necessary for the drive operation (Setup Mode)

    • See and set all parameters (Parameter Setting Mode)

    • Automatically set motor parameters (Auto-Tuning Mode)

Table 1 gives information about the functions you can access when you push [Up arrow key] / [Down arrow key].

Note:

Set b1-08 [Run Command Select in PRG Mode] to accept or reject the Run command from an external source when in Programming Mode.

  • Set b1-08 = 0 [Disregard RUN while Programming] to reject the Run command from an external source while in Programming Mode.

  • Set b1-08 = 1 [Accept RUN while Programming] to accept the Run command from an external source while in Programming Mode.

  • Set b1-08 = 2 [Allow Programming Only at Stop] to prevent changes from Drive Mode to Programming Mode.

Table 1. Overview of the Modes

Mode

LED Display

Description

Description

Ref.

Drive Mode

(Operation of the motor and monitoring of operation status)

[Frequency reference display]

Frequency reference display

You can set and monitor frequency references.

Note:

You can change what is shown on the keypad when you energize the drive. Use o1-02 [Monitor Selection at Power-up] to set the items. When A1-02 = 6 [Control Method Selection = AOLV/PM], the display unit is %.

-

[Monitor display]

Monitor display

The keypad shows Ux-xx [Monitor].

-

[Output voltage display]

Output voltage display

You can monitor the output voltage reference.

Set o1-01 [User Monitor Selection] to change the item shown on this screen.

Parameter List

[Output current display]

Output current display

You can monitor the output current.

-

[Output frequency display]

Output frequency display

You can monitor the frequency output from the drive.

-

[Forward/reverse selection]

Forward/reverse selection

[Forward selection]: Motor rotates in forward direction

[Reverse selection]: Motor rotates in reverse direction

Note:

For applications where the motor must not rotate in reverse direction (for example, for fans and pumps), you can use b1-04 [Reverse Operation Selection] to prevent reverse rotation.

How to set reverse operation [Reverse selection]

-

Programming Mode

(Parameter Settings)

[Auto-Tuning Mode]

Auto-Tuning Mode

The drive automatically calculates and sets the motor parameters.

Auto-Tuning for Induction Motors

Auto-Tuning for PM Motors

Auto-Tuning in EZ Open Loop Vector Control Method

[Parameter Setting Mode]

Parameter Setting Mode

You can see and set all parameters.

Change Parameter Settings

[Setup Mode]

Setup Mode

Shows and sets basic parameters necessary for drive operation.

Note:

The parameters shown in the Setup Mode are different for different A1-06 [Application Preset] settings.

Setup Mode

Automatic Parameter Settings Optimized for Specific Applications (Application Presets)

[Verify Menu]

Verify Menu

Lists all parameters that are not at their default settings.

Verify and Set the Changed Parameters (Verify Menu)