You can select and register a maximum of 12 monitoring items to regularly show on the keypad.

This procedure shows how to set the motor speed to [Custom Monitor 1].

  1. Push [F2 Key] (Home) to show the HOME screen.
    Note:
    • The keypad will show [Home] in the top right corner when the HOME screen is active.

    • If the keypad does not show [Home] on [F2 Key], push [F1 Key] (Back) to show [Home] on [F2 Key].

  2. Push [F2 Key] (Menu).
  3. Push [Up arrow key] or [Down arrow key] to select [Monitors], then push [ENTER Key].
  4. Push [Up arrow key] or [Down arrow key] to select [Custom Monitor], then push [F3 Key] (Setup).
  5. Push [Up arrow key] or [Down arrow key] to select [Custom Monitor 1], then push [ENTER Key].
  6. Push [Up arrow key] or [Down arrow key] to select the monitor number to register, then push [ENTER Key].

    Set the x-xx part of monitor Ux-xx. For example, to show monitor U1-05, set it to “105” as shown in this figure.

The configuration procedure is complete.