The procedure in this section shows how to set the trigger for data logging. Note: This setting is available only when you select short-term data log as the data log type. Push (Home) to show the HOME screen. Note: When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen. If the screen does not show [Home] for , push (Back) and then push to show [Home]. Push (Menu). Push or to select [Diagnostic Tools], then push . Push or to select [Data Logger], then push (Setup). Push or to select [Log Trigger], then push . Push or to select [Trigger Type Selection], then push . Push or to select the type of trigger, then push . Note: There are no detection width or detection time settings for the analog trigger in the data log function. If variations in the analog signal are a problem, select the digital trigger and use o5-16 = 66/67 [Digital Trigger Object = Comparator 1/2]. Use H2-20 [Comparator 1 Monitor Selection] to H2–32 [Comparator 1 Filter Time] to set the conditions for the comparator function. Push or to select [Trigger Object], then push . Push or to select the trigger target, then push . Note: If analog trigger is the trigger type, set the trigger target and trigger level. Push or to select [Trigger Condition], then push . Push or to select the trigger detections, then push . Push or to select [Pre-Trigger Setting], then push . Push or then push or to change the value. After you change the value, push . The procedure to set the trigger is complete.