No. (Hex.) Name Description Default (Range) Ref. H4-01 (041D) Terminal AM Analog Output Select Sets the monitoring number to be output from the MFAO terminal AM. Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02 [Output Frequency]. 102 (000 - 999) Details No. (Hex.) Name Description Default (Range) Ref. H4-02 (041E) RUN Terminal AM Analog Output Gain Sets the gain of the monitor signal that is sent from MFAO terminal AM. Sets the analog signal output level from the terminal AM at 10 V or 20 mA as 100% when an output for monitoring items is 100%. 100.0% (-999.9 - +999.9%) Details No. (Hex.) Name Description Default (Range) Ref. H4-03 (041F) RUN Terminal AM Analog Output Bias Sets the bias of the monitor signal that is sent from MFAO terminal AM. When an output for monitoring items is 0%, this parameter sets the analog signal output level from the AM terminal at 10 V or 20 mA as 0%. 0.0% (-999.9 - +999.9%) Details No. (Hex.) Name Description Default (Range) Ref. H4-07 (0423) Terminal AM Signal Level Select Sets the MFAO terminal AM output signal level. Note: Make sure that you set jumper S5 on the control circuit terminal board when you change these parameters. 0 0-10V 2 4 to 20 mA 0 (0, 2) Details No. (Hex.) Name Description Default (Range) Ref. H4-20 (0B53) Analog Power Monitor 100% Level Sets the level at 10 V when U1-08 [Output Power] is set for analog output. 0.00 kW (0.00 - 650.00 kW) Details