YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C5-01
(021B)
RUN
ASR Proportional Gain 1
Sets the gain to adjust ASR response.
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Determined by A1-02
(0.00 - 300.00)
Details
C5-02
(021C)
ASR Integral Time 1
Sets the ASR integral time.
(0.000 - 60.000 s)
C5-03
(021D)
ASR Proportional Gain 2
C5-04
(021E)
ASR Integral Time 2
C5-05
(021F)
ASR Limit
Sets the ASR output limit where E1-04 [Maximum Output Frequency] is 100%.
5.0%
(0.0 - 20.0%)
C5-06
(0220)
ASR Delay Time
Sets the filter time constant of the torque reference output from the speed loop. Usually it is not necessary to change this setting.
(0.000 - 0.500 s)
C5-07
(0221)
ASR Gain Switchover Frequency
Sets the frequency where the drive will switch between these parameters: C5-01 and C5-03 [ASR Proportional Gain 1/2]C5-02 and C5-04 [ASR Integral Time 1/2]
(Determined by A1-02)
C5-08
(0222)
ASR Integral Limit
Set the upper limit of the ASR integral amount as a percentage of the rated load.
400%
(0 - 400%)
C5-12
(0386)
Integral Operation @ Accel/Decel
Sets ASR integral operation during acceleration and deceleration.
Integral operation is not enabled during acceleration or deceleration. Integral operation is always enabled during constant speed.
Integral operation is always enabled.
0
(0, 1)
C5-29
(0B18)
Expert
Speed Control Response
Sets the level of speed control responsiveness. Usually it is not necessary to change this setting.
1
C5-39
(030D)
ASR Primary Delay Time Const 2
Sets the filter time constant used when the torque reference is output from ASR. Usually it is not necessary to change this parameter.
0.000 s